Omni-Chill Packaged Chillers | Dry Coolers Inc.

Dry Coolers Inc.

Industrial Process Cooling Systems

Dry Coolers, Inc.
575 South Glaspie Street
Oxford, MI 48371 USA

1-800-525-8173

Omni-Chill Packaged Chillers

Brochure Code
ACU-150

If you're running city or well water through your machinery for cooling — you're wasting money. With water bills and sewer charges increasing at a rapid pace with no relief in sight, it's time to consider "closing the loop." A low maintenance Omni-Chill packaged water chiller recirculates your water through a refrigerant system giving you in expensive, reliable heat transfer.

Complete systems include integral pumping systems, electrical control panels and full refrigerant safety controls. Standard systems are pre-charged and ready to run. Water cooled and air cooled units are avail able from 1/2 ton through 200 tons. Options include: non-ferrous construction, casters, hot gas bypass for reduced load operation, emergency back up cooling systems, etc. Dry Coolers can meet almost any specification with a standard or custom built cooling package.

Stop wasting valuable fresh water for process cooling. Look into our easy to install packaged chiller units today. One of our knowledgeable application engineers will be ready to assist you in designing a more efficient method of cooling your process. An Omni-Chill chiller is compact in size, but big in quality and reliability.

Rapid payback, industrial construction and well-engineered design make the Omni-Chill packaged chiller unit a winner on all fronts. The emphasis is on reliability for industrial process applications.

FEATURES

  • Air Cooled or Water Cooled Condensers
  • Digital Indicating Microprocessor Temperature Controller
  • Flow Switch & Low Temp Alarm for Freeze Protection
  • High & Low Refrigerant Pressure Indication
  • Direct Drive Propeller Fans (Air Cooled Condenser Models)
  • Water Regulating Valve (Water Cooled Condensers)
  • Crankcase Heater & Suction Line Accumulator
  • Filter Drier & Refrigerant Sight Glass
  • Insulated Water Lines & Reservoir
  • Rugged Steel Housing — Removable for Easy Access
  • Pre-Charged & Pre-Wired for Easy Installation

Model AC-300A shown with side panels and top removed and optional casters.


MODEL COMPR.
HP
CAPACITY
BTU/hr
PUMP
HP
CHILLED
WATER GPM
TOTAL FLA CONDENSER
WATER GPM
CONNECTIONS WEIGHT
LBS.
230V 1Ø 230V 3Ø 460V 3Ø PROCESS COND.
AIR COOLED AC-075A 3/4 8,400 1/3 1.7 13.6 3/4" 380
AC-100A 1 11,400 1/3 2.3 13.6 8.5 3/4" 390
AC-150A 1 1/2 16,800 1/2 3.4 21.3 16.5 3/4" 415
AC-200A 2 21,600 1/2 4.3 24.0 15.2 7.8 3/4" 490
AC-300A 3 33,600 3/4 6.7 40.8 26.5 13.0 1" 515
WATER COOLED AC-100W 1 16,200 1/3 3.2 14.8 4.0 3/4" 3/4" 390
AC-150W 1 1/2 19,200 1/2 3.8 18.4 13.6 6.1 4.8 3/4" 3/4" 410
AC-200W 2 25,200 1/2 5.0 21.7 12.9 6.3 6.3 1" 1" 435
AC-300W 3 40,800 3/4 8.2 35.0 20.7 9.8 10.3 1" 1 1/4" 465
AC-400W 4 55,200 1 11.0 46.4 26.0 12.6 13.8 1 1/4" 1 1/4" 545
AC-500W 5 63,600 1 12.7 50.8 30.4 13.8 15.9 1 1/4" 1 1/4" 550

Note: 1 Chiller Ton = 12,000 BTU/hr. Capacities are based upon 60°F entering water, 50°F leaving water at 90°F ambient or 85°F condenser water.

Specifications are subject to change without notice. Please consult factory for certified prints and performance.